W-F-1814/2C
REQUIREMENTS:
Interface and physical dimensions: See figure 1. Physical: Nonrenewable.
Terminals: Ferrule type.
Material: Brass, copper, or copper alloy.
Strength: 2 pound-inches torque between body and ferrules. Body:
Insulating material: Fiber, ceramic, melamine-impregnated glass fiber, or other suitable material. Electrical:
Voltage: 600 volts or less. Frequency: 48 Hz to 60 Hz. Current: See table l.
Current carrying capacity: 100 percent indefinitely with temperature rise not to exceed 75°C
above ambient on the ferrules.
Overload interrupt:
Instantaneous: Shall interrupt within 1 hour at 135 percent of rated current and within
4 minutes at 200 percent of rated current.
Time delay: In addition to the above requirement, the fuse shall not interrupt
200 percent of rated current within 12 seconds. Watts loss: Average not to exceed 2.5 watts.
Interrupting capacity rating: 100,000 amperes rms symmetrical at 600 volts, 60 Hz, and power factor of 20 percent or less.
Threshold ratio: 60 maximum.
Peak let-thru current: 5,000 amperes maximum. Maximum clearing: I2T - 5x103 ampere2 seconds.
Applicable fuseholders: Class G in accordance with UL 4248-5.
Part or Identifying Number (PIN): See table l.
2