W-F-1814/63E
Interrupting capacity rating: 200,000 amperes rms symmetrical at 600 volts, 48 to 60 Hz and a power factor of 20 percent or less. Closing angle shall be essentially at the zero of the voltage wave (maximum offset) or later, to produce start of arcing within 30 electrical degrees prior to system peak voltage.
Threshold ratio: 30 maximum for RK1; 65 maximum for RK5. Peak let-thru current: See table II.
Maximum clearing I2T: See table II.
Applicable fuseholder: Class R for ferrule type fuses in accordance with UL 4248-12.
Part or Identifying Number (PIN): The Government PIN shall consist of the prefix "WF1814/63-" followed by the PIN designation shown in table I.
TABLE I. Current rating and PIN designation.
Current in amperes |
PIN designation |
|||
RK5 |
RK1 |
|||
Instantaneous |
Time delay |
Instantaneous |
Time delay |
|
35 40 45 50 60 |
F535 F540 F545 F550 F560 |
0535 0540 0545 0550 0560 |
F135 F140 F145 F150 F160 |
0135 0140 0145 0150 0160 |
TABLE II. Peak let-thru and I2T current.
Between threshold and 50 kA |
100 kA |
200 kA |
||||
RK1 |
RK5 |
RK1 |
RK5 |
RK1 |
RK5 |
|
Maximum acceptable peak let-thru current (Ip x 103) |
10 |
20 |
12 |
21 |
16 |
26 |
Maximum clearing I2T (amperes squared seconds) (I2T x 103) |
40 |
200 |
40 |
200 |
50 |
200 |
Referenced documents. In addition to W-F-1814, this document references the following: UL 4248-12
The margins of this specification sheet are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in these notations. Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue.
3
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business