MIL-PRF-15160/40C
TABLE II. Overload interrupt.
Percent
Current
Characteristic
nominal
range
rating
A
B
1/ 135
40 A to 60 A
0 to 1 hour
0 to 1 hour
70 A to 150 A
0 to 2 hours
0 to 2 hours
300
All ratings
N/A
15 seconds minimum
1/ The overload interrupt test at 135 percent shall be performed at 32 volts
or less.
VERIFICATION:
Qualification inspection is not applicable for 40A, 50A, 75A, 100A, 125A, and 150A characteristic A
fuses and all characteristic B fuses of this specification sheet (see table l) and shall be replaced by
acceptance testing consisting of Group A and Group B inspections per MIL-PRF-15160, prior to
delivery.
Qualification inspection (Characteristic A only): The number of qualification samples required shall be:
a. 24 samples maximum current rating of each voltage and design.
b. 24 samples minimum current rating of each voltage and design.
The margins of this specification sheet are marked with vertical lines to indicate where changes from the
previous issue were made. This was done as a convenience only and the Government assumes no
liability whatsoever for any inaccuracies in these notations. Bidders and contractors are cautioned to
evaluate the requirements of this document based on the entire content irrespective of the marginal
notations and relationship to the last previous issue.