MIL-PRF-23419/9D
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Applicable fuseholders (or equivalent):
MIL-PRF-19207/1, Style FHL10U
MIL-PRF-19207/2, Style FHL11U
MIL-PRF-19207/8, Style FHL17G
MIL-PRF-19207/9, Style FHL18G
MIL-PRF-19207/11, Style FHL20G
MIL-PRF-19207/16, Style FHL26G
MIL-PRF-19207/17, Style FHL28WB
MIL-PRF-19207/18, Style FHL29G
MIL-PRF-19207/19, Style FHL30G
MIL-PRF-19207/21, Style FHL32W
MIL-PRF-19207/22, Style FHL33W
Terminals: Ferrule type.
Material: Brass, copper, or copper alloy.
Finish: Nickel or bright alloy plate, silver plated when specified.
Terminal strength: Method 211 of MIL-STD-202, test condition E, 2 pound-inch torque between ferrules and fuse
body.
Body material: Plastic or ceramic tube.
Current rating: See table I.
Characteristic: See table I.
Voltage rating: See table I.
Current-carrying capacity for 20 amperes or less:
110 percent at room ambient temperature:
Characteristic A: 112.5 percent at -55°C, 91.5 percent at +85°C.
Characteristic B: 119 percent at -55°C, 69.5 percent at +85°C.
Current-carrying capacity for 25 amperes or 30 amperes:
100 percent with a maximum temperature rise of +90°C for all temperatures between -55°C and +85°C.
Characteristic: See table I.
Overload interrupt: See table I (at all temperatures between -55°C and +85°C).
Resistance: See table I.
Short circuit interrupt: See table I.
Mechanical shock: Method I.
2