W-F-1814/56D
TABLE II. Peak let-thru and I2T current.
Between threshold and 50 kA |
100 kA |
200 kA |
||||
RK1 |
RK5 |
RK1 |
RK5 |
RK1 |
RK5 |
|
Maximum acceptable peak let-thru current (I x 103) p |
6 |
11 |
10 |
11 |
12 |
14 |
Maximum clearing I2T (amperes squared seconds) (I2T x 103) |
10 |
50 |
10 |
50 |
11 |
50 |
Referenced documents. In addition to W-F-1814, this document references the following: UL 4248-12
The margins of this specification sheet are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in these notations. Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue.
MILITARY INTEREST: CIVIL AGENCY COORDINATING ACTIVITIES: Custodians: GSA - FAS
Army - CR
Navy - EC Preparing activity: Air Force - 85
DLA - CC DLA - CC
Review activities: (Project 5920-2013-014) Army - AR, AT, CR4
Navy - OS NSA - NS
NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.